Smart Building Cybersecurity - BMS Threats and Protection
Contents
  1. What Is a Smart Building and Why It Is Vulnerable
  2. How Attackers Exploit BMS
  3. Who Is Responsible for Smart Building Security
  4. Protecting Smart Building Systems
  5. Regulatory Requirements
  6. Smart Building Security Checklist
  7. Where We Help
  8. Legal and Normative Basis
  9. Sources

A failure of a building management system (BMS) stops the server room cooling, switches off access control and forces people to evacuate. Building administrators often do not know which building devices are reachable from the internet and learn about it only after an incident.

A 2025 Claroty study shows how widespread the exposure of BMS is:

Indicator Value What it means
Devices examined more than 467,000 in 529 organizations The scope of the Claroty sample.
Organizations with known exploited vulnerabilities (KEV) in BMS 75% Three of four organizations have a vulnerability from the exploited-vulnerabilities catalog in their BMS.
Organizations with KEVs used in confirmed ransomware attacks 69% A large share of these vulnerabilities has already been used by ransomware groups.
Organizations with a BMS that has a KEV and is insecurely connected to the internet 51% Claroty combines vulnerability and exposure here.

Source: Claroty Team82, State of CPS Security 2025: Building Management System Exposures.

What Is a Smart Building and Why It Is Vulnerable

A smart building is a facility where building automation systems integrate the management of heating, ventilation and air conditioning (HVAC), lighting, access control, surveillance, elevators and fire systems. Such systems operate in office buildings, shopping malls, hospitals, airports, data centers and hotels.

Building automation protocols include BACnet, KNX and LONworks. Many installations use them without authentication and encryption, as the table below shows.

BMS Protocols - Security Status

The table shows which protections each protocol has and which secure versions exist.

Protocol Standard Authentication Encryption Secure version
BACnet ASHRAE 135 BACnet/IP does not authenticate communication. BACnet/IP does not encrypt communication. BACnet/SC (ASHRAE 135-2020) mutually authenticates connections and encrypts them with TLS 1.3.
KNX EN 50090 KNX Classic does not authenticate communication. KNX Classic does not encrypt communication. KNX Secure encrypts communication with AES-128 CCM.
LONworks ANSI/CEA-709 LonTalk has optional sender authentication with a 48-bit key. LonTalk does not encrypt data. The sources of this article do not name a version with encryption.
Modbus TCP Modbus.org Modbus/TCP does not authenticate communication. Modbus/TCP does not encrypt communication. Modbus/TCP Security (2018 specification) uses TLS.

Installed devices may not support the secure versions, so the building owner first checks which devices do. The sources of this article do not describe how widely the secure versions are deployed.

How Attackers Exploit BMS

Internet Exposure

Exposing a BMS to the internet, often unknowingly, creates the shortest path to a building system. An internet exposure scanner detects BACnet (UDP 47808), KNX (UDP 3671) and Modbus (TCP 502) devices reachable from outside. The 2025 Claroty report on OT exposures states that 40% of the organizations studied have some OT assets insecurely connected to the internet.

At the end of January 2024 Forescout counted nearly 110,000 ICS/OT devices reachable from the internet. The count relies on the ICS tag of an internet device search engine and, according to the authors, covers many but not all devices. KNX, BACnet and Tridium Fox together accounted for about 32% of them.

Many such systems are protected by a default password or none. In 2019 researcher Paul Kane of Safety Detective found more than 7,000 RDM refrigeration systems on the internet with a default password, among them systems at retail chains and at a hospital in the United Kingdom.

Contractor Access and Integration with the Corporate Network

BMS are usually serviced by external companies: installers, maintenance and building service providers. Their accounts form a path into the owner’s network.

In 2013 attackers entered the network of the US retailer Target with credentials of an HVAC service provider, Fazio Mechanical. Fazio stated that its connection to Target served billing, contract submission and project management, not remote control of installations. The case is not an attack on a BMS. It shows, however, that a building service provider’s account opens a path into the client’s network.

The building owner should therefore know three topologies that increase risk:

  1. A BMS controller with direct internet access. A flat network without segmentation lets anyone reach the controller from outside.
  2. A BMS connected to the corporate network for energy reporting. Such a layout lets an attacker move from the IT network to building systems and back.
  3. A BMS managed from the manufacturer’s cloud. The manufacturer’s platform then becomes part of the building’s attack surface.

A copy of each controller’s configuration must be kept. Why: after a controller is compromised, it has to be restored from a trusted configuration.

Attack Examples and Incidents

The table lists cases in which a building system or its supplier was the target or the path of access.

Incident Year Target Impact
Google, Sydney 2013 Niagara BMS at the Google office. Cylance researchers gained access to the BMS as a demonstration.
Target (USA) 2013 Target’s network, entered with credentials of an HVAC service provider. Theft of data of about 40 million payment cards. The BMS was not the attack path.
Johnson Controls 2023 Ransomware in the IT infrastructure of a building systems manufacturer. According to an SEC filing, an impact of about 27 million USD on the company’s net income.

Who Is Responsible for Smart Building Security

Responsibility for BMS security is spread across the whole building life cycle. The investor, the general contractor, the BMS installers and the security systems integrator take part in the project. Later the building is handled by administration, service companies and the tenants’ IT departments.

The investor should clarify four matters at every stage:

  • The designer takes cybersecurity into account when designing BMS.
  • Device purchasing takes into account the manufacturer’s security and its process for reporting vulnerabilities.
  • Building acceptance includes security testing of the whole system.
  • Someone verifies the security status during operation and receives time and resources for it.

Writing these four matters into the contractor’s contract gives the investor a basis to demand corrections.

Protecting Smart Building Systems

Segmentation - The First Line of Defense

The IEC 62443 zones and conduits model applies to buildings the same way as to industrial plants. The BMS must be placed in its own zone, separated from the corporate network by a firewall. Why: a compromised office computer then cannot reach the controllers, and a BMS failure does not stop the IT network.

Remote access to the BMS should pass through a controlled point at the zone boundary, for example an intermediary server, with multi-factor authentication. IEC 62443-3-3 requires control of communication at zone boundaries. The choice of a concrete solution follows from the risk assessment under IEC 62443-3-2.

Minimum set of segmentation rules for a smart building:

  1. Place the BMS in a separate virtual local area network (VLAN) with its own firewall. Why: the firewall limits traffic to the necessary connections.
  2. Disable routing from the BMS to the internet. Why: a controller that does not reach the internet does not expose services and cannot be used for hidden communication.
  3. Allow remote access only through a controlled point with multi-factor authentication. Why: a single stolen password is no longer enough.
  4. Monitor BACnet and Modbus traffic with a passive intrusion detection system (IDS). Why: passive monitoring does not affect the operation of controllers.
  5. Separate safety systems (fire protection, surveillance, process protection systems) from the BMS. Why: a failure or compromise of the BMS must not weaken the protection of people.

Protocol Hardening

New installations must require BACnet/SC and KNX Secure. Why: both versions encrypt communication, and BACnet/SC also authenticates connections. In existing installations compensating measures are introduced: segmentation, monitoring and access control to configuration panels.

Asset Inventory

Most BMS operators cannot list all connected devices. Inventory is the starting point, because without it nobody can decide what to protect. Passive traffic monitoring detects building devices without affecting their operation.

Regulatory Requirements

NIS2

The NIS2 Directive covers medium-sized and large entities from 18 critical sectors, among them energy, transport, health, finance, water management and digital infrastructure. An entity covered by the directive is responsible for the systems whose failure affects its service, including the BMS. A failed air conditioning of a hospital operating room is an example of an incident the entity assesses for a notification duty to the national authority. The status of the national law implementing NIS2 should be checked in its current text, because this article does not describe it.

EU Cyber Resilience Act

The CRA regulation covers products with digital elements, that is hardware and software made available on the EU market, including BMS components. Since 11 September 2026 manufacturers report actively exploited vulnerabilities and severe incidents: an early warning within 24 hours and a notification within 72 hours. The main requirements for products, including security by design and a software bill of materials (SBOM), apply from 11 December 2027. The investor should ask the BMS supplier how it handles vulnerability reports for its products.

IEC 62443

The IEC 62443 standard divides duties among three roles. The facility owner mainly uses part 2-1 (security program). The integrator bases the design on parts 3-2 (risk assessment and zone partitioning) and 3-3 (system requirements). The manufacturer is responsible for parts 4-1 (product development process) and 4-2 (component requirements). An IEC 62443 audit assesses the conformity of a BMS with the standard’s requirements.

Smart Building Security Checklist

The checklist leads from inventory to procedures. Each row describes an action to take.

Area Item What to do
Inventory BMS device register Record all controllers, sensors and actuators together with firmware version and address.
BMS network map Draw the network topology and mark connections to the IT network and the internet.
Segmentation Separate BMS network Separate the BMS from the IT network with a VLAN and a firewall.
Isolation of safety systems Place fire protection, surveillance and process protection systems in a separate segment.
No access from the internet No BMS device is reachable directly from the internet.
Access Change of default passwords Change administrative passwords on every device.
Multi-factor authentication Enable it for remote access through a VPN or a management portal.
Individual service accounts Give each employee of a service company their own account.
Monitoring Protocol monitoring Monitor BACnet, KNX and Modbus traffic with a passive intrusion detection system.
Access logs Record all remote sessions and configuration changes.
Updates Controller firmware Check regularly whether the manufacturer has published an update.
SBOM Ask the supplier for the list of software components in BMS devices.
Procedures Response plan Keep a procedure for an attack on BMS.
Change management Apply a management of change (MOC) procedure to every BMS configuration change.

Where We Help

Smart building security starts with inventory and segmentation. This approach implements the defense in depth principle and does not require replacing the whole installation. We assess the conformity of a BMS with the standard in an IEC 62443 audit, and we check the resilience of a building’s OT network to attack in penetration testing.

Topic Where it is
Reporting of actively exploited vulnerabilities and severe incidents by manufacturers CRA, provisions on manufacturer reporting obligations; applies from 11 September 2026
Main requirements for products with digital elements CRA, applies from 11 December 2027
Scope of entities and reporting of significant incidents NIS2 Directive (EU 2022/2555), provisions on scope and incident reporting
Control of communication at zone boundaries IEC 62443-3-3, SR 5.2
Risk assessment and zone partitioning IEC 62443-3-2

Sources

  1. Claroty Team82 - State of CPS Security 2025: Building Management System Exposures - Claroty (accessed: )
  2. (TLP:CLEAR) Claroty Report Highlights Elevated Risk to OT Systems - WaterISAC (accessed: )
  3. Cybersecurity threat evolution of OT/ICS and IoT devices - Forescout (accessed: )
  4. Refrigeration Systems Used by Supermarkets, Hospitals Left Exposed Online - SecurityWeek (accessed: )
  5. Google left heating, cooling system open to hackers - CSO Online (accessed: )
  6. Target Hackers Broke in Via HVAC Company - Krebs on Security (accessed: )
  7. Target Breach: HVAC Contractor Systems Investigated - Dark Reading (accessed: )
  8. Johnson Controls says ransomware attack cost $27 million, data stolen - BleepingComputer (accessed: )
  9. Protecting Building Automation Systems with BACnet Secure Connect - ASHRAE (accessed: )
  10. Introduction to the LonWorks Platform - Echelon (accessed: )
  11. Cyber Resilience Act - reporting obligations - European Commission (accessed: )
  12. Cyber Resilience Act - European Commission (accessed: )
  13. NIS2 Directive - European Commission (accessed: )