Secure PLC coding
The Top 20 Secure PLC Coding Practices. Part 9 - Validate HMI input variables at the PLC level, not only at HMI
Part 9 of Top 20 Secure PLC Coding Practices: why HMI input must also be range-checked inside the PLC, not only at the HMI.
Eugen WypiorPublished 5 min read
Contents
- **HMI access to PLC variables can (and should) be restricted to a valid operational value range at the HMI, but further cross-checks in the PLC should be added to prevent, or alert on, values outside of the acceptable ranges which are programmed into the HMI. **
- Guidance
- Example
- Why?
- References
- Practical example
- What’s next?
- Do you require help with secure coding of your PLCs?
- If you have any questions or require help in securely coding your PLCs, please contact SEQRED. SEQRED specialises in providing bespoke OT and IoT cybersecurity solutions. Our services cover such areas as Critical Infrastructure Protection, Cloud Services Security or Audits, and Threat Intelligence. For a full list of our services visit our services page – https://seqred.pl/en/services/
- About this article
Part 9 of the Top 20 Secure PLC Coding Practices series, originally published by admeritia GmbH (Langenfeld, Germany). SEQRED reproduces the series under the open license granted by the copyright holder. Full specification: plc-security.com.
**HMI access to PLC variables can (and should) be restricted to a valid operational value range at the HMI, but further cross-checks in the PLC should be added to prevent, or alert on, values outside of the acceptable ranges which are programmed into the HMI. **
| Security Objective | Target Group |
|---|---|
| Integrity of PLC variables | Product Supplier Integration / Maintenance Service Provider |
Guidance
Input validation could include out-of-bounds checks for valid operational values as well as valid values in terms of data types that are relative to the process.
If a PLC variable receives a value that is out-of-bounds, provide PLC logic to either
- input a default value to that variable which does not negatively affect the process, and can be used as a flag for alerts, or
- input the last correct value to that value and log the event for further analysis.
Example
Example 1
An operation requires a user to input a value on an HMI for valve pressure. Valid ranges for this operation are 0-100, and the user’s input is passed from the user input function on the HMI to the V1 variable in the PLC. In this case,
1. HMI input to variable V1 has a restricted range of 0-100 (dec.) programmed into the HMI.
2. The PLC has a cross-check logic that states:
IF V1 < 0 OR IF V1 > 100, SET V1 = 0.
This provides a positive response of a presumably safe value to an invalid input to that variable.
Example 2
**** An operation requires user input for measurement thresholds to a variable that should always be within an INT2 data range. The user input is passed from the HMI into the V2 variable in the PLC, which is a 16-bit data register.
1. HMI input to variable V2 has a restricted range of -32768 to 32767 (dec.) programmed into the HMI.
2. The PLC has data-type cross-check logic that monitors the overflow variable (V3), which exists just after V2 in the PLC’s memory structure:
IF V2 = -32768 OR IF V2 = 32767 AND V3 != 0,
SET V2 = 0 AND SET V3 = 0 AND SET DataTypeOverflowAlarm = TRUE.
Example 3
Scale PV (Process Value), SP (Set Point) and CV (Control Variable) for PID (Proportional, Integral, Derivative controller) to consistent or raw units to eliminate scaling errors causing control problem. Incorrect scaling might lead to inadvertent abuse cases.
Why?
| Beneficial for …? | Why? |
|---|---|
| Security | 1. While HMIs typically provide some sort of input validation, a malicious actor can craft or replay modified packets to send arbitrary values to the variables in the PLC which are open to outside influence (open to values passed from an HMI, for example). 2. PLC protocols are typically marketed as “open” protocols and published to the general public, so creating malware that utilizes “open” protocol information can be trivial to develop. PLC variable mapping can typically occur through traffic analysis during the reconnaissance phases of an attack, thus providing the intruder with the necessary information to craft malicious traffic to the target and thereby manipulate a process with unauthorized tools. Cross-checking values passed into the PLC before implementing that data into the process ensures valid data ranges and mitigates an invalid value in those memory locations by forcibly setting safe ranges when a value is detected as out-of-bounds during the course of the PLC scan. |
| **Reliability ** | / |
| **Maintenance ** | / |
References
| Standard / framework | Mapping |
|---|---|
| **MITRE ATT &CK for ICS ** | Tactic:TA010 - Impair Process Control Technique:T0836 - Modify Parameter |
| **ISA 62443-3-3 ** | SR 3.5 : Input validation SR 3.6 : Deterministic Output |
| **ISA 62443-4-2 ** | CR 3.5 : Input validation CR 3.6 : Deterministic Output |
| **ISA 62443-4-1 ** | SI-2 : Secure coding standards SVV-1: Security requirements testing |
| MITRE CWE | 1320: Improper Protection for Out of Bounds Signal Level Alerts |
Practical example
Arnaud SOULLIÉ gives a practical example for the reason to validate HMI input variables at the PLC level not only at HMI in a short video (see the link in sources under the article).
What’s next?
In the next article of The Top 20 Secure PLC Coding Practices series, you will find out about validating indirections.
Do you require help with secure coding of your PLCs?
If you have any questions or require help in securely coding your PLCs, please contact SEQRED. SEQRED specialises in providing bespoke OT and IoT cybersecurity solutions. Our services cover such areas as Critical Infrastructure Protection, Cloud Services Security or Audits, and Threat Intelligence. For a full list of our services visit our services page – https://seqred.pl/en/services/
About this article
This article is reproduced from the Top 20 Secure PLC Coding Practices project coordinated by Sarah Fluchs (admeritia GmbH) and Vivek Ponnada (Nozomi Networks), with support from ISA Global Cybersecurity Alliance and S4 Events.
The full copy of the document is available at plc-security.com.
License
Copyright (c) 2021 admeritia GmbH, Langenfeld/Rheinland, Germany.
Permission is hereby granted, free of charge, to any person obtaining a copy of “Top 20 Secure PLC Coding Practices” and associated documentation files, to deal in the work without restriction, including the rights to use, copy, modify, merge, publish, distribute, sublicense, and/or sell copies, subject to preserving this copyright notice.
The work is provided “as is”, without warranty of any kind. Full license at plc-security.com.