Secure PLC coding
The Top 20 Secure PLC Coding Practices. Part 7 - Validate timers and counters
Integrity of PLC variables | Integration / Maintenance Service Provider
Eugen WypiorPublished 4 min read
Contents
- If timers and counters values are written to the PLC program, they should be validated by the PLC for reasonableness and verify backward counts below zero
- Guidance
- Example
- Why?
- References
- Practical example
- What’s next?
- Do you require help with secure coding of your PLCs?
- If you have any questions or require help in securely coding your PLCs, please contact SEQRED. SEQRED specialises in providing bespoke OT and IoT cybersecurity solutions. Our services cover such areas as Critical Infrastructure Protection, Cloud Services Security or Audits, and Threat Intelligence. For a full list of our services visit our services page – https://seqred.pl/en/services/
- About this article
Part 7 of the Top 20 Secure PLC Coding Practices series, originally published by admeritia GmbH (Langenfeld, Germany). SEQRED reproduces the series under the open license granted by the copyright holder. Full specification: plc-security.com.
If timers and counters values are written to the PLC program, they should be validated by the PLC for reasonableness and verify backward counts below zero
| Security Objective | Target Group |
|---|---|
| Integrity of PLC variables | Integration / Maintenance Service Provider |
| Asset Owner |
Guidance
Timers and counters can technically be preset to any value. Therefore, the valid range to preset a timer or counter needs to/should be restricted to meet the operational requirements.
If remote devices such as an HMI write timer or counter values to a program:
- do not let the HMI write to the timer or counter directly but go through a validation logic
- validate presets and timeout values in the PLC
Validation of timer and counter inputs is easy to be done directly in the PLC (without the need for any network device capable of Deep Packet Inspection), since the PLC “knows” what the process state or context is. It can validate “what’ it gets and “when” it gets the commands or setpoints.
Example
During PLC startup, timers and counters are usually preset to certain values.
If there is a timer that triggers alarms at 1.3 seconds, but that timer is preset maliciously to 5 minutes, it might not trigger the alarm.
If there is a counter that causes a process to stop when it reaches 10,000 but that is set to 11,000 from the beginning, the process might not stop.
Why?
| Beneficial for …? | Why? |
|---|---|
| Security | If I/O, timers, or presets are written directly to I/O, not being validated by the PLC, the PLC validation layer is evaded and the HMI (or other network devices) are assigned an unwarranted level of trust. |
| **Reliability ** | The PLC can also validate when an operator accidentally presets bad timer or counter values. |
| **Maintenance ** | Having valid ranges for timers and counters documented and automatically validated may help when updating logic. |
References
| Standard / framework | Mapping |
|---|---|
| **MITRE ATT &CK for ICS ** | Tactic:TA010 - Impair Process Control Technique:T0836 - Modify Parameter |
| **ISA 62443-3-3 ** | SR 3.5 : Input validation |
| **ISA 62443-4-2 ** | CR 3.5 : Input validation |
| **ISA 62443-4-1 ** | SI-2 : Secure coding standards SVV-1: Security requirements testing |
Practical example
Arnaud SOULLIÉ gives a practical example for the reason to validate timers and counters in a short video (see the link in sources under the article).
What’s next?
In the next article of The Top 20 Secure PLC Coding Practices series, you will find out about validating and alerting for paired inputs / outputs.
Do you require help with secure coding of your PLCs?
If you have any questions or require help in securely coding your PLCs, please contact SEQRED. SEQRED specialises in providing bespoke OT and IoT cybersecurity solutions. Our services cover such areas as Critical Infrastructure Protection, Cloud Services Security or Audits, and Threat Intelligence. For a full list of our services visit our services page – https://seqred.pl/en/services/
About this article
This article is reproduced from the Top 20 Secure PLC Coding Practices project coordinated by Sarah Fluchs (admeritia GmbH) and Vivek Ponnada (Nozomi Networks), with support from ISA Global Cybersecurity Alliance and S4 Events.
The full copy of the document is available at plc-security.com.
License
Copyright (c) 2021 admeritia GmbH, Langenfeld/Rheinland, Germany.
Permission is hereby granted, free of charge, to any person obtaining a copy of “Top 20 Secure PLC Coding Practices” and associated documentation files, to deal in the work without restriction, including the rights to use, copy, modify, merge, publish, distribute, sublicense, and/or sell copies, subject to preserving this copyright notice.
The work is provided “as is”, without warranty of any kind. Full license at plc-security.com.
See also
- SEQRED’s synthesis article: Top 20 Secure PLC Coding Practices - a condensed guide
- Full series: browse all 21 parts under the
secure codingtag